Table 6-3: Protection Device Capacity
Model
(Input P: Bypass P:
Output P)
With RT-15K3P
With RT-20K3P
(3:3:3)
50A/ Type D (main)
50A/ Type D (bypass)
63A/ Type D (main)
63A/ Type D (bypass)
(3:1:1)
50A/ Type D (main)
100A/ Type D (bypass)
63A/ Type D (main)
125A/ Type D (bypass)
The section provides general guidance for qualified installation engineers. A
qualified installation engineer should be aware of local wiring regulations and other
relevant knowledge.
NOTE:
1. For dual-source input configurations, the main AC source and the
bypass source must use the same neutral (N).
2. The three-phase UPS must be equipped with four-pole protection
devices to cut off the power from four cables, and the single-phase UPS
must be equipped with two-pole protection devices to cut off the power
from 2 cables.