33
Amplon
RT
Series
3. Under the cover plate, there is a manual bypass detector (see Figure 8-2)
that will be automatically activated to send the UPS a message of
transferring into bypass mode once the cover plate is removed. After you
confirm that the UPS has been run in bypass mode, turn on the manual
bypass switch. Now, the connected loads are being powered by utility
power. Please see
Figure 8-2
(
Figure 8-2: Turn on the MBB Manual Bypass Switch
)
4. Disassemble the provided cover on the three power cables (You can refer to
Figure 6-12
).
5. Disconnect the main input cable and bypass input cable first to turn off the
output of UPS then disconnect the output cable and the MBB
Summary of Contents for Amplon MBB RT Series