Chapter 11 Description of Parameter Settings
|
C200 Series
11-9
1kHz
8kHz
15kHz
Carrier
Frequency
Acoustic
Noise
Electromagnetic
Noise or Leakage
Current
Heat
Dissipation
Current
Wave
Significant
Minimal
Minimal
Minimal
Significant
Significant
From the table, we see that the PWM carrier frequency has a significant influence on the
electromagnetic noise, AC motor drive heat dissipation, and motor acoustic noise. Therefore, if the
surrounding noise is greater than the motor noise, lower the carrier frequency is good to reduce the
temperature rise. Although it is quiet operation in the higher carrier frequency, the entire wiring and
interference resistance should be considerate.
When the carrier frequency is higher than the factory setting, it needs to protect by decreasing the
carrier frequency. See Pr.06-55 for the related setting and details.
Single or Three-phase setting
Factory Setting: Read Only
Settings 0: 3-phase
1: 1-phase
When Pr.00-00=2, 00-18=0 : 230V, 0.4kW, 3-Phase
Pr.00-00=2, 00-18=1 : 230V, 0.4kW, 1-Phase
Pr.00-00=4, 00-18=0 : 230V, 0.75kW, 3-Phase
Pr.00-00=4, 00-18=1 : 230V, 0.75kW, 1-Phase
Pr.00-00=5, 00-18=0 : 460V, 0.75kW
Pr.00-00=6, 00-18=0 : 230V, 1.5kW, 3-Phase
Pr.00-00=6, 00-18=1 : 230V, 1.5kW, 1-Phase
Pr.00-00=7, 00-18=0 : 460V, 1.5kW
Pr.00-00=8, 00-18=0 : 230V, 2.2kW, 3-Phase
Pr.00-00=8, 00-18=1 : 230V, 2.2kW, 1-Phase
Pr.00-00=9, 00-18=0 : 460V, 2.2kW
Pr.00-00=10, 00-18=0 : 230V, 3.7kW, 3-Phase
Pr.00-00=11, 00-18=0 : 460V, 3.7kW
Pr.00-00=13, 00-18=0 : 230V, 5.5kW
Pr.00-00=15, 00-18=0 : 460V, 7.5kW
Pr.00-00=93, 00-18=0 : 460V, 4.0kW
PLC Command Mask
Factory Setting: Read Only
Settings Bit 0: Control command by PLC force control
Bit 1: Frequency command by PLC force control
This parameter determines if frequency command or control command is occupied by PLC