Chapter 11 Description of Parameter Settings
|
C200 Series
11-28
OFF: contact is open)
Settings
Functions
Descriptions
0 No
Function
1
Multi-step speed command
1/multi-step position command
1
2
Multi-step speed command 2/
multi-step position command 2
3
Multi-step speed command 3/
multi-step position command 3
4
Multi-step speed command 4/
multi-step position command 4
15 step speeds could be conducted through the digital status of the 4
terminals, and 16 in total if the master speed is included. (Refer to
Parameter set 4)
5 Reset
After the error of the drive is eliminated, use this terminal to reset the
drive.
6 JOG
Command
Before executing this function, it needs to wait for the drive stop
completely. During running, it can change the operation direction and
STOP key on the keypad is valid. Once the external terminal
receives OFF command, the motor will stop by the JOG deceleration
time. Refer to Pr.01-20~01-22 for details.
01-20
01-21
O N
OFF
MIx-GND
01-22
JOG frequency
01-07
Min. output frequency
of motor 1
JOG accel. time
JOG decel. time
7
Acceleration/deceleration
Speed Inhibit
When this function is enabled, acceleration and deceleration is
stopped. After this function is disabled, the AC motor drive starts to
accel./decel. from the inhibit point.
ON
ON
ON
ON
ON
OFF
MIx-GND
Frequency
Operation
command
Time
Setting
frequency
Actual operation frequency
Actual operation
frequency
Accel. inhibit
area
Accel. inhibit
area
Decel. inhibit
area
Decel. inhibit
area
8
The 1
st
, 2
nd
acceleration or
deceleration time selection
9
The 3
rd
, 4
th
acceleration or
deceleration time selection
The acceleration/deceleration time of the drive could be selected from
this function or the digital status of the terminals; there are 4
acceleration/deceleration speeds in total for selection.
10
EF Input (EF: External fault)
External fault input terminal. It will decelerate by Pr.07-20 setting (it
will have fault record when external fault occurs)
11
External B.B. Input (Base
Block)
When this contact is ON, output of the drive will be cut off immediately,
and the motor will be free run and display B.B. signal. Refer to
Pr.07-08 for details.
12 Output
Stop
If this contact is ON, output of the drive will be cut off immediately, and
the motor will then be free run. And once it is turned to OFF, the drive
will accelerate to the setting frequency.