Chapter 11 Description of Parameter Settings
|
C200 Series
11-34
44: Low current output (Pr.06-71 to Pr.06-73)
45: Reserved
46: Master dEb action output
47: Closed brake output
48~49: Reserved
50: Output for CANopen control
51: Output for RS-485
This parameter is used for setting the function of multi-function terminals.
Summary of function settings (Take the normally open contact for example, ON: contact is closed,
OFF: contact is open)
Settings
Functions
Descriptions
0 No
Function
1
Operation Indication Active when the drive is not at STOP.
2
Master Frequency
Attained
Active when the AC motor drive reaches the output frequency setting.
3
Desired Frequency
Attained 1 (Pr.02-22) Active when the desired frequency (Pr.02-22) is attained.
4
Desired Frequency
Attained 2 (Pr.02-24) Active when the desired frequency (Pr.02-24) is attained.
5
Zero Speed
(frequency
command)
Active when frequency command =0. (the drive should be at RUN
mode)
6
Zero Speed with Stop
(frequency
command)
Active when frequency command =0 or stop.
7 Over
Torque
1
Active when detecting over-torque. Refer to Pr.06-07 (over-torque
detection level-OT1) and Pr.06-08 (over-torque detection time-OT1).
Refer to Pr.06-06~06-08.
8 Over
Torque
2
Active when detecting over-torque. Refer to Pr.06-10 (over-torque
detection level-OT2) and Pr.06-11 (over-torque detection time-OT2).
Refer to Pr.06-09~06-11.
9
Drive Ready
Active when the drive is ON and no abnormality detected.
10
Low voltage warn
(Lv)
Active when the DC Bus voltage is too low. (refer to Pr.06-00 low
voltage level)
11
Malfunction Indication Active when fault occurs (except Lv stop).
12
Mechanical Brake
Release (Pr.02-32)
When drive runs after Pr.02-32, it will be ON. This function should be
used with DC brake and it is recommended to use contact ”b”(N.C).
13 Overheat
Active when IGBT or heat sink overheats to prevent OH turn off the
drive. (refer to Pr.06-15)
14
Software Brake
Signal Indication
Active when the soft brake function is ON. (refer to Pr.07-00)
15
PID Feedback Error Active when the feedback signal is abnormal.
16
Slip Error (oSL)
Active when the slip error is detected.
17
Terminal Count Value
Attained (Pr.02-20;
not return to 0)
Active when the counter reaches Terminal Counter Value (Pr.02-19).
This contact won’t active when Pr.02-20>Pr.02-19.
18
Preliminary Counter
Value Attained
(Pr.02-19; returns to
0)
Active when the counter reaches Preliminary Counter Value
(Pr.02-19).
19
External Base Block
input (B.B.)
Active when the output of the AC motor drive is shut off during base
block.
20
Warning Output
Active when the warning is detected.
21
Over-voltage Warning Active when the over-voltage is detected.
22
Over-current Stall
Prevention Warning Active when the over-current stall prevention is detected.