Chapter 11 Description of Parameter Settings
|
C200 Series
11-35
Settings
Functions
Descriptions
23
Over-voltage Stall
prevention Warning Active when the over-voltage stall prevention is detected.
24
Operation Mode
Indication
Active when the operation command is controlled by external
terminal. (Pr.00-20
≠
0)
25
Forward Command Active when the operation direction is forward.
26
Reverse Command Active when the operation direction is reverse.
27
Output when Current
>= Pr.02-33
Active when current is >= Pr.02-33.
28
Output when Current
<= Pr.02-33
Active when current is <= Pr.02-33.
29
Output when
frequency >=
Pr.02-34
Active when frequency is >= Pr.02-34.
30
Output when
Frequency <=
Pr.02-34
Active when frequency is <= Pr.02-34.
31
Y-connection for the
Motor Coil
Active when PR.05-24 is less than Pr.05-23 and time is more than
Pr.05-25.
32
-connection for the
Motor Coil
Active when PR.05-24 is higher than Pr.05-23 and time is more than
Pr.05-25.
33
Zero Speed (actual
output frequency)
Active when the actual output frequency is 0. (the drive should be at
RUN mode)
34
Zero Speed with Stop
(actual output
frequency)
Active when the actual output frequency is 0 or Stop.
35
Error Output
Selection 1 (Pr.06-23) Active when Pr.06-23 is ON.
36
Error Output
Selection 2 (Pr.06-24) Active when Pr.06-24 is ON.
37
Error Output
Selection 3 (Pr.06-25) Active when Pr.06-25 is ON.
38
Error Output
Selection 4 (Pr.06-26) Active when Pr.06-26 is ON.
39 Reserved
40
Speed Attained
(including zero
speed)
Active when the output frequency reaches frequency setting or stop.
41 Reserved
42 Crane
Function
This function should be used with Pr.02-32, Pr.02-33 and Pr.02-34.
Active when setting Pr.07-16=Pr.02-34 and Fcmd > Pr.02-34 and
output current > Pr.02-33 and Time > Pr.02-32.
The example of the crane application is in the following for your
reference.
43
Motor Zero-speed
Output (Pr.02-47)
Active when motor actual speed is less than Pr.02-47.
44
Low Current Output This function needs to be used with Pr.06-71 ~ Pr.06-73
45
Reserved
46
Master dEb signal
output
When dEb arise at Master, MO will send a dEb signal to Slave. Then
Slave will follow Master’s command and decelerate to stop
simultaneously.
47
Brake Release at
Stop
When drive stops, the corresponding multi-function terminal will be
ON if the frequency is less than Pr.02-34. After it is ON, it will be OFF
when brake delay time exceeds Pr.02-32.