Chapter 11 Description of Parameter Settings
|
C200 Series
11-62
Factory Setting: 100.0
Settings -500.0~500.0%
Parameters 03-03 to 03-14 are used when the source of frequency command is the analog
voltage/current signal.
Analog Input Filter Time (AVI)
Analog Input Filter Time (ACI)
Analog Input Filter Time (AUI)
Factory Setting: 0.10
Settings 0.00~2.00 sec
These input delays can be used to filter noisy analog signal.
When the setting of the time constant is too large, the control will be stable but the control response
will be slow. When the setting of time constant is too small, the control response will be faster but
the control may be unstable. To find the optimal setting, please adjust the setting according to the
control stable or response status.
Addition Function of the Analog Input
Factory Setting: 0
Settings 0: Disable (AVI, ACI, AUI)
1: Enable
When Pr.03-18 is set to 0 and the analog input setting is the same, the priority for AVI, ACI and AUI
are AVI>ACI>AUI.
Fco mmand= [(ay bias)*gain] * Fmax(01-00)
10V or 16mA
ay : 10 or 16mA
bias : Pr.03-03,Pr. 03-04, Pr.0 3-05
gain : Pr.03 -11 , Pr.03-12, Pr. 03-13, Pr.0 3-14
Frequ ency
Voltage
Fcomma nd: the co rresponding
frequen cy for 10V or 20mA
Treatment to 4-20mA Analog Input Signal Loss
Factory Setting: 0
Settings 0: Disable
1: Continue operation at the last frequency
2: Decelerate to stop
3: Stop immediately and display ACE
This parameter determines the behavior when 4~20mA signal is loss, when AVI(Pr.03-28=2) or ACI
(03-29=0).
When Pr.03-28 is not set to 2, it means the voltage input to AVI terminal is 0-10V or 0-20mA. At this
moment, Pr.03-19 will be invalid.
When Pr.03-29 is set to 1, it means the voltage input to ACI terminal is for 0-10V. At this moment,
Pr.03-19 will be invalid.
When setting is 1 or 2, it will display warning code “AnL” on the keypad. It will be blinking until the