Chapter 11 Description of Parameter Settings
|
C200 Series
11-66
4: Serve bias as the center
Refer to Pr.03-07~03-09.
Keypad potentiometer input Gain
Factory
Setting:100.0
Settings -500.0~500.0%
AFM1 DC output setting level Keypad potentiometer analog Input Filter Time
Factory
Setting:0.01
Settings 0~2.00 sec.
~
Reserve
Analog Input Curve Selection
Factory Setting: 0
Settings 0: Regular Curve
1: 3 point curve of AVI
2: 3 point curve of ACI
3: 3 point curve of AVI & ACI
4: 3 point curve of AUI
5: 3 point curve of AVI & AUI
6: 3 point curve of ACI & AUI
7: 3 point curve of AVI & ACI & AUI
AVI Low Point
Factory Setting: 0.00
Settings 03-28=0, 0.00~10.00V
03-28
≠
0, 0.00~20.00mA
AVI Proportional Low Point
Factory Setting: 0.00
Settings 0.00~100.00%
AVI Mid Point
Factory Setting: 5.00
Settings 03-28=0, 0.00~10.00V
03-28
≠
0, 0.00~20.00mA
AVI Proportional Mid Point
Factory Setting: 50.00
Settings 0.00~100.00%
AVI High Point
Factory Setting: 10.00