Chapter 11 Description of Parameter Settings
|
C200 Series
11-67
Settings 03-28=0, 0.00~10.00V
03-28
≠
0, 0.00~20.00mA
AVI Proportional High Point
Factory Setting: 100.00
Settings 0.00~100.00%
When Pr.03-28 = 0, AVI
setting is 0-10V and the unit is in voltage (V).
When Pr.03-28
≠
0, AVI setting is 0-20mA or 4-20mA and the unit is in current (mA).
When setting analog input AVI to frequency command, it 100% corresponds to Fmax (Pr.01-00
Max. operation frequency).
Three of the AVI points can be set according to user’s demand on voltage(current) and proportion,
there is no setting limit for ACI points.
ACI Low Point
Factory Setting: 4.00
Settings Pr.03-29=1, 0.00~10.00V
Pr.03-29
≠
1, 0.00~20.00mA
ACI Proportional Low Point
Factory Setting: 0.00
Settings 0.00~100.00%
ACI Mid Point
Factory Setting: 12.00
Settings 03-29=1, 0.00~10.00V
03-29
≠
1, 0.00~20.00mA
ACI Proportional Mid Point
Factory Setting: 50.00
Settings 0.00~100.00%
ACI High Point
Factory Setting: 20.00
Settings 03-29=1, 0.00~10.00V
03-29
≠
1, 0.00~20.00mA
ACI Proportional High Point
Factory Setting: 100.00
Settings 0.00~100.00%
When Pr.03-29=1, ACI setting is 0-10V and the unit is in voltage (V).
When Pr.03-29
≠
1, ACI setting is 0-20mA or 4-20mA and the unit is in current (mA).
When setting analog input ACI to frequency command, it 100% corresponds to Fmax (Pr.01-00
Max. operation frequency).
Three of the ACI points can be set according to user’s demand on voltage (current) and proportion,
there is no setting limit for ACI points.
Positive AUI Voltage Low Point
Factory Setting: 0.00