Chapter 11 Description of Parameter Settings
|
C200 Series
11-68
Settings 0.00~10.00V
Positive AUI Voltage Proportional Low Point
Factory Setting: 0.00
Settings 0.00~100.00%
Positive AUI Voltage Mid Point
Factory Setting: 5.00
Settings 0.00~10.00V
Positive AUI Voltage Proportional Mid Point
Factory Setting: 50.00
Settings 0.00~100.00%
Positive AUI Voltage High Point
Factory Setting: 10.00
Settings 0.00~10.00V
Positive AUI Voltage Proportional High Point
Factory Setting: 100.00
Settings 0.00~100.00%
When setting positive voltage AUI to frequency command, it 100% corresponds to Fmax (Pr.01-00
Max. operation frequency) and the motor runs in forward direction.
Three of the positive voltage AUI points can be set according to user’s demand on voltage and
proportion, there is no setting limit for AUI points.
Negative AUI Voltage Low Point
Factory Setting: 0.00
Settings 0.00~-10.00V
Negative AUI Voltage Proportional Low Point
Factory Setting: 0.00
Settings 0.00~-100.00%
Negative AUI Voltage Mid Point
Factory
Setting:
-5.00
Settings 0.00~-10.00V
Negative AUI Voltage Proportional Mid Point
Factory
Setting:
-50.00
Settings 0.00~-100.00%
Negative AUI Voltage High Point
Factory
Setting:
-10.00
Settings 0.00~-10.00V
Negative AUI Voltage Proportional High Point
Factory
Setting:
-100.00
Settings 0.00~-100.00%
When setting negative voltage AUI to frequency command, it 100% corresponds to Fmax (Pr.01-00
Max. operation frequency) and the motor runs in reverse direction.