Chapter 11 Description of Parameter Settings
|
C200 Series
11-81
Output
frequency
Deceleration c har acteristic
when Ov er-Voltage Stall
Pr ev ention enabled
Frequenc y Held
previous deceleration time
Time
Time
High-voltage
at DC si de
Ov er-v ol tage
detec ti on
level
requir ed time for decelerating to 0Hz when over- voltage
stall prevention is enabled.
Selection for Over-voltage Stall Prevention
Factory Setting: 0
Settings 0: Traditional over-voltage stall prevention
1: Smart over-voltage prevention
When Pr.06-02 is set to 1, the drive will maintain DCbus voltage when decelerating and prevent
OV.
Output Frequency
DCBUS Voltage
310Vdc
370Vdc
Time
230V Series
60Hz
0
Over-current Stall Prevention during Acceleration
Settings Normal duty: 0~160% (100%: drive’s rated current)
Factory Setting: 120
Heavy duty: 0~180% (100%: drive’s rated current)
Factory Setting: 150
If the motor load is too large or drive acceleration time is too short, the AC drive output current may
increase abruptly during acceleration and it may cause motor damage or trigger protection
functions (OL or OC). This parameter is used to prevent this situation.