Chapter 11 Description of Parameter Settings
|
C200 Series
11-88
62: Decel. Energy Backup Error (dEb)
63: Slip error (oSL)
64: Electromagnet switch error (ryF)
65 : PG Card Error (PGF5)
66-78: Reserved
79: Uocc U phase over current (Detection begins as RUN is pressed,
software protection)
80: Vocc V phase over current (Detection begins as RUN is pressed,
software protection)
81: Wocc W phase over current (Detection begins as RUN is pressed,
software protection)
82: OPHL U phase output phase loss
83: OPHL Vphase output phase loss
84: OPHL Wphase output phase loss
85~100: Reserved
101: CGdE CANopen software disconnect1
102: CHbE CANopen software disconnect2
103: CSYE CANopen synchronous error
104: CbFE CANopen hardware disconnect
105: CIdE CANopen index setting error
106: CAdE CANopen slave station number setting error
107: CFrE CANopen index setting exceed limit
108~110: Reserved
111: InrCOM Internal communication overtime error
When th
e fault occurs and force stopping, it will record in this parameter.
At stop with low voltage Lv (LvS warn, no record). During operation with mid-low voltage Lv (LvA,
Lvd, Lvn error, will record).
Setting 62: when dEb function is enabled, the drive will execute dEb and record to the Pr.06-17 to
Pr.06-22 simultaneously.
Fault Output Option 1
Fault Output Option 2
Fault Output Option 3
Fault Output Option 4
Factory Setting: 0
Settings 0 to 65535 sec (refer to bit table for fault code)
These parameters can be used with multi-function output (set to 35-38) for the specific
requirement. When the fault occurs, the corresponding terminals will be activated (It needs
to convert binary value to decimal value to fill in Pr.06-23 to Pr.06-26).
Bit0
Bit1
Bit2
Bit3
Bit4
Bit5
Bit6
Fault Code
current Volt.
OL
SYS FBK
EXI
CE
0:
No
fault
1: Over-current during acceleration (ocA)
●