Chapter 2 Installation
|
C200 Series
2-3
NO T E
※
The mounting clearances stated in the figure is for installing the drive in an
open area. To install the drive in a confined space (such as cabinet or
electric box), please follow the following three rules: (1) Keep the minimum
mounting clearances. (2) Install a ventilation equipment or an air
conditioner to keep surrounding temperature lower than operation
temperature. (3) Refer to parameter setting and set up Pr. 00-16, Pr.00-17,
and Pr. 06-55.
※
The following table shows the heat dissipation and the required air
volume when installing a single drive in a confined space. When
installing multiple drives, the required air volume shall be multiplied
by the number the drives.
※
Refer to the chart (Air flow rate for cooling) for ventilation equipment
design and selection.
※
Refer to the chart (Power dissipation) for air conditioner design and
selection.
Air flow rate for cooling
Power dissipation of AC motor drive
Power Dissipation
Model No.
Flow Rate
(cfm)
Flow Rate
(m
3
/hr)
Loss External
(Heat sink)
Internal Total
VFD004CB21A-20/-21/-21M
- -
16 20 36
VFD007CB21A-20/-21/-21M
- -
32 39 72
VFD015CB21A-20/-21/-21M 15
26
60
52
112
VFD022CB21A-20/-21/-21M 15
26
85
69
154
VFD004CB23A-20/-21/-21M
- -
21 17 37
VFD007CB23A-20/-21/-21M
- -
35 26 61
VFD015CB23A-20/-21/-21M
15 26 56
32
89
VFD022CB23A-20/-21/-21M 15
26
82
34
116
VFD037CB23A-20/-21/-21M
15
26 118 43 161
VFD007CB43A-20/-21/-21M -
-
35
24
59
VFD015CB43A-20/-21/-21M -
-
47
27
74
VFD022CB43A-20/-21/-21M 15
26
75
30
105
VFD037CB43A-20/-21/-21M
15
26 110 33 143
VFD040CB43A-20/-21/-21M 15
26
126
34
160
VFD055CB43A-20/-21/-21M 15
26
145
37
181
VFD075CB43A-20/-21/-21M 24
41
212
83
295
※
The required airflow shown in chart is for installing
single drive in a confined space.
※
When installing the multiple drives, the required air
volume should be the required air volume for single
drive X the number of the drives.
※
The heat dissipation shown in the chart is
for installing single drive in a confined
space.
※
When installing the multiple drives,
volume of heat dissipation should be the
heat dissipated for single drive X the
number of the drives.
※
Heat dissipation for each model is
calculated by rated voltage, current and
default carrier.