Chapter 11 Description of Parameter Settings
|
C200 Series
11-96
230V
Pr.06-55=1
Pr.06-55=0 or 2
(50
℃
: UL open-type)
(40
℃
:UL type1 or open type_size by size)
100
110
90
80
70
50
2
5 6 7 8 9 10 11 12 13 14 15
Fc
(kHz)
R
a
ti
o
(%
)
VFD004~037CB23A
VFD004~022CB21A
60
40
4
3
230V
Pr.06-55=0 or 2
(40
℃
: UL open-type)
(30
℃
: UL type1 or open type_size by size)
100
110
90
80
70
50
2
5 6 7 8 9 10 11 12 13 14 15
Fc
(kHz)
R
a
ti
o
(%
)
VFD004~037CB23A
VFD004~022CB21A
60
40
4
3
NOTE
※
The mounting clearances stated in the figure is for installing the drive in
an open area. To install the drive in a confined space (such as cabinet
or electric box), please follow the following three rules: (1) Keep the
minimum mounting clearances. (2) Install a ventilation equipment or an
air conditioner to keep surrounding temperature lower than operation
temperature. (3) Refer to parameter setting and set up Pr. 00-16,
Pr.00-17, and Pr. 06-55.
※
The following table shows heat dissipation and the required air volume
when installing a single drive in a confined space. When installing
multiple drives, the required air volume shall be multiplied by the
number the drives.
※
Refer to the chart (Air flow rate for cooling) for ventilation equipment
design and selection.
※
Refer to the chart (Power dissipation) for air conditioner design and
selection.
Minimum mounting clearances:
Frame
A (mm)
B (mm)
C (mm)
D (mm)
A~C
60 30 10
0
Air flow rate for cooling
Power Dissipation
Model No.
Flow Rate
(cfm)
Flow Rate
(m
3
/hr)
Loss External
(Heat sink)
Internal
Total
VFD004CB21A-20/-21/-21M
- -
16 20 36
VFD007CB21A-20/-21/-21M
- -
32 39 72
VFD015CB21A-20/-21/-21M 15
26
60
52
112
VFD022CB21A-20/-21/-21M 15
26
85
69
154
VFD004CB23A-20/-21/-21M
- -
21 17 37
VFD007CB23A-20/-21/-21M
- -
35 26 61
VFD015CB23A-20/-21/-21M
15 26 56
32
89
VFD022CB23A-20/-21/-21M 15
26
82
34
116
VFD037CB23A-20/-21/-21M 15
26
118
43
161
VFD007CB43A-20/-21/-21M -
-
35
24
59
VFD015CB43A-20/-21/-21M -
-
47
27
74
VFD022CB43A-20/-21/-21M 15
26
75
30
105
VFD037CB43A-20/-21/-21M 15
26
110
33
143
VFD040CB43A-20/-21/-21M 15
26
126
34
160
VFD055CB43A-20/-21/-21M 15
26
145
37
181
VFD075CB43A-20/-21/-21M 24
41
212
83
295
※
The required airflow shown in chart is for installing one
※
The heat dissipation shown in the chart is for