Chapter 11 Description of Parameter Settings
|
C200 Series
11-97
drive in confined space.
※
When installing the multiple drives, the required air volume
should be the required air volume for single drive X the
number of the drives.
installing single drive in a confined space.
※
When installing multiple drives, volume of heat
dissipation should be the heat dissipated for single
drive X the number of the drives.
※
Heat dissipation for each model is calculated by
rated voltage, current and default carrier.
~
Reserved
Software Detection GFF Current Level
Factory Setting: 60.0
Settings 0.0~6553.5 %
Software Detection GFF Filter Time
Factory Setting: 0.10
Settings 0.0~6553.5 %
Disable Level of dab
Factory Setting: 180.0/360.0
Settings 230V series: 0.0~220.0 Vic
460V series: 0.0~440.0 Vic
Fault Record 1 (min)
Fault Record 2 (min)
Fault Record 3 (min)
Fault Record 4 (min)
Fault Record 5 (min)
Fault Record 6 (min)
Factory Setting: Read only
Settings 0~64799 min
Pr.06-63 to Pr.06-68 are used to record the operation time for 6 malfunctions and it can also check
if there is any wrong with the drive according to the internal time.
When the malfunction occurs during operation, it records fault in Pr.06-17~06-22 and operation
time is recorded in Pr.06-63~06-68.
For example: When the first fault ovA occurs after operation 3000 min., second fault ovd occurs at
3482 min., third fault ovA occurs at 4051 min., fourth fault ocA at 5003 min., fifth fault ocA at 5824
min., sixth fault ocd occurs at 6402 min. and seven fault ocS at 6951 min..
It’ll be recorded as the following table: