Chapter 11 Description of Parameter Settings
|
C200 Series
11-105
function is the AC motor drive decelerates to stop after momentary power loss. When the
momentary power loss occurs, this function can be used for the motor to decelerate to 0 speed with
deceleration stop method. When the power is on again, motor will run again after DEB return time.
(has applied on high-speed spindle)
Status 1: Insufficient power supply due to momentary power-loss/unstable power (due to low
voltage)/sudden heavy-load
07-14
NOTE
DC BUS voltage
it doesn't need
multi-function terminals
The level for DEB return time
(Lv=+30V+58V)
Lv level
Soft start relay at
power side
Output frequency
DEB return time
Pr.07-13 Decel. time selection for
momentary power loss
DEB function is activated
The level for soft start relay to be ON
(Lv+30)
When Pr.07-14 is set to 0, the AC motor drive will be stopped and won't re-start
at the power-on again.
Status 2: unexpected power off, such as momentary power loss
DC BUS voltage
The level for DEB return time
(Lv=+30V+58V)
Lv level
Soft start relay at
power side
Output frequency
DEB return time
Pr.07-13 Decel. time selection for
momentary power loss
DEB function is activated
The level for soft start relay to be ON
(Lv+30)
07-14
NOTE
For example, in textile machinery, you will hope that all the machines can be decelerated to stop to prevent broken stitching
when power loss. In this case, the host controller will send a message to the AC motor drive to use dEb function with
deceleration time via EF.
Dwell Time at Accel.
Factory Setting: 0.00
Settings 0.00~600.00 sec
Dwell Frequency at Accel.
Factory Setting: 0.00