Chapter 11 Description of Parameter Settings
|
C200 Series
11-116
Settings 0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: Warn and operate at last frequency
This parameter is valid only when the feedback signal is ACI.
AC motor drive acts when the feedback signals (analog PID feedback or PG (encoder) feedback)
are abnormal.
Sleep Frequency
Factory Setting: 0.00
Settings Pr.08-18=0: 0.00~600.00Hz
Pr.08-18=1: 0.00~200.00%
Wake-up Frequency
Factory Setting: 0.00
Settings Pr.08-18=0: 0.00~600.00Hz
Pr.08-18=1: 0.00~200.00%
Sleep Time
Factory Setting: 0.0
Settings 0.00~6000.0 sec
If the command frequency falls below the sleep frequency, for the specified time in Pr. 08-12, then
the drive will shut off the output and wait until the command frequency rises above Pr.08-11.
08-11
08-10
08-12
0Hz
Sleep Function
Frequency command
actual output frequency
sleep time
Wake-up frequency
Sleep frequency
PID Deviation Level
Factory Setting: 10.0
Settings 1.0~50.0%
PID Deviation Time
Factory Setting: 5.0
Settings 0.1~300.0 sec
Filter Time for PID Feedback
Factory Setting: 5.0
Settings 0.1~300.0 sec
When the PID control function is normal, it should calculate within a period of time and close to the
setpoint value.
Refer to the PID control diagram for details. When executing PID feedback control, if |PID
reference target value – detection value| > Pr.08-13 PID Deviation Level and exceeds Pr.08-14