Chapter 11 Description of Parameter Settings
|
C200 Series
11-117
setting, the PID control fault occurs. The treatment will be done as Pr.08-09 setting.
PID Compensation Selection
Factory Setting: 0
Settings 0: Parameter setting
1: Reserved
PID Compensation
Factory Setting: 0
Settings -100.0~+100.0%
Setting of Sleep Mode Function
Factory Setting: 0
Settings 0: Follow PID output command
1: Follow PID feedback signal
Wake-up Integral Limit
Factory Setting: 50.0
Settings 0.0~200.0%
The upper limit when the VFD is at sleep mode to avoid running at high speed right after being
waken up.
There are three types of Sleep mode and Wakeup mode.
01: Frequency command(Not using PID, Pr08-00=0)
Output Frequency Sleep Frequency, the drive goes to Sleep mode, 0Hz.
≦
P r. 08-11
Wak e up
f requenc y
Pr.08-12
Sleep Time
0H z
P r. 08-10
S leep f requenc y
Frequenc y C ommand
S leep Mode D iagram
Actual Output Frequency
when functioning
02: Internal PID Frequency Calculation Command (Not using PID, Pr08
≠
0)
When arriving at the sleep frequency, the system starts to calculating sleep time and the output
frequency starts to decrease. If it passes the preset sleep time, the system will go to seelp at 0Hz.
If the system is not yet reaching the preset sleep time, (if there is a preset) or will stay at Pr01-07,
waiting to reach the sleep time then go to sleep at 0Hz.