Chapter 11 Description of Parameter Settings
|
C200 Series
11-118
Frequency
output freq.
Pr.08-11
w ake up freq.
Pr.08-10
Sleep freq.
Pr.01-11
Output freq.
lower limit
Pr.01-07/Pr.01-41
Pr.08-12
Sleep Time
Time
Deceleration
time limit
Acceleration
time limit
03: Percentage of PID’s Target Value (Set PID, Pr08-00
≠
0)
When reaching the percentage of PID’s Target Value and the percentage of the feedback value,
the system.
Starts to calculate the sleep time. The output frequency decreases immediately. If the system
passes the preset sleep time, it will go to sleep at 0Hz. However, if it doesn’t reach the preset
sleep time, it will remain at Pr01-11 (if there is a preset value) or Pr01-07 waiting to reach the
sleep tiem then go to sleep at 0Hz.
Frequency
Pr 08 10
Sleep freq
.
-
.
Pr 08 11
wake up freq.
.
-
Time
Output Freq.
PID
Feedback value
Pr 08 12
Sleep time
.
-
Enable or disable the Sleep and Wakeup functions depends on the setting of Pr08-10. When
Pr08-10=0, it means Disable, while Pr08-10
≠
0, it means Enable.
Enable PID to Change the Operation Direction
Factory Setting: 0
Settings 0: Disable change of direction
1: Enable change of direction