Chapter 11 Description of Parameter Settings
|
C200 Series
11-119
09 Communication Parameters
The parameter can be set during the operation.
Pin 1~2,7,8: Reserv ed
Pin 3, 6: GND
Pin 4: SG-
Pin 5: SG+
RS-485
8
1
Modbus RS- 485
When us ing communication devi ces,
connects AC dr ive with P C by us ing
Delta IFD6530 or IFD6500.
COM1 Communication Address
Factory Setting: 1
Settings 1~254
If the AC motor drive is controlled by RS-485 serial communication, the communication address
for this drive must be set via this parameter. And the communication address for each AC motor
drive must be different and unique.
COM1 Transmission Speed
Factory Setting: 19.2
Settings 4.8~115.2 Kbps
This parameter is used to set the transmission speed between the RS485 master (PLC, PC, etc.)
and AC motor drive.
COM1 Transmission Fault Treatment
Factory Setting: 3
Settings 0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning and continue operation
This parameter is set to how to react if transmission errors occur.
COM1 Time-out Detection
Factory Setting: 0.0
Settings 0.0~100.0 sec
0.0: Disable
It is used to set the transmission time between communication and keypad.
COM1 Communication Protocol
Factory Setting: 13
Settings 1: 7, N, 2 for ASCII
2: 7, E, 1 for ASCII
3: 7, O, 1 for ASCII
4: 7, E, 2 for ASCII
5: 7, O, 2 for ASCII
6: 8, N, 1 for ASCII
7: 8, N, 2 for ASCII
8: 8, E, 1 for ASCII