Chapter 11 Description of Parameter Settings
|
C200 Series
11-126
Content Address
Function
Bit 4-5
00B: No function
01B: FWD
10B: REV
11B: Change direction
Bit
6-7
00B: 1st accel/decel
01B: 2nd accel/decel
10B: 3rd accel/decel
11B: 4th accel/decel
Bit 8-11 000B: master speed
0001B: 1st accel/decel.
0010B:
2nd
accel/decel
0011B: 3rd accel/decel
0100B:
4th
accel/decel
0101B:
5th
accel/decel
0110B: 6th accel/decel
0111B:
7th
accel/decel
1000B:
8th
accel/decel
1001B:
9th
accel/decel
1010B: 10th accel/decel
1011B:
11th
accel/decel
1100B:
12th
accel/decel
1101B:
13th
accel/decel
1110B: 14th accel/decel
1111B: 15th accel/decel
Bit 12
1: enable bit06-11 function
Bit 13~14 00B: No function
01B: operated by digital keypad
10B: operated by Pr.00-21 setting
11B: change operation source
Bit
15
Reserved
2001H Frequency
command
Bit 0
1: EF (external fault) on
Bit 1
1: Reset
Bit 2
1: B.B. ON
Command
Write only
2002H
Bit 3-15 Reserved
Status monitor
Read only
2100H
Error code: refer to Pr.06-17 to Pr.06-22
2101H
Bit0
Bit1
AC Drive Operation Status
00b: Drive stops
01b: Drive decelerating
10b: Drive standby
11b: Drive operating
Bit2
1: JOG Command
Bit3
Bit4
Operation Direction
00b: FWD run
01b: from REV run to FWD run
10b: REV run
11b: from FWD run to REV run
Bit8
1: Master frequency controlled by communication
interface
Bit9
1: Master frequency controlled by analog signal
Bit10
1: Operation command controlled by
communication interface
Bit11
1: Parameter locked
Bit12
1: Enable to copy parameters from keypad
Bit13~15
Reserved
2102H Frequency command (F)