Chapter 11 Description of Parameter Settings
|
C200 Series
11-127
Content Address
Function
2103H Output
frequency
(H)
2104H Output current (AXX.X.X)
2105H DC-BUS Voltage (UXXX.X)
2106H Output voltage (EXXX.X)
2107H Current step number of Multi-Step Speed Operation
2108H
Reserved
2109H
Counter
value
210AH Power Factor Angle (XXX.X)
210BH
Output
Torque
(%)
210CH Actual motor speed (rpm)
210DH Number of PG feed back pulses
210FH
Power
output
(X.XXX)
2116H Multi-function display (Pr.00-04)
211BH Max. opeartion frequency (Pr.01-00) or Max. user defined value
(Pr.00-26)
2200H Display output current (A)
2201H Display counter value of TRG terminal (c)
2202H Display actual output frequency (H)
2203H Display DC-BUS voltage (u)
2204H Display output voltage of U, V, W (E)
2205H Display output power angle of U, V, W (n)
2206H Display actual motor speed kW of U, V, W (P)
2207H Display motor speed in rpm estimated by the drive or encoder
feedback (r00: positive speed, -00: negative speed)
2208H Display positive/negative output torque in %, estimated by the
drive (t0.0: positive torque, -0.0: negative torque)
220AH Display PID feedback value after enabling PID function in % (b)
220BH Display signal of AVI analog input terminal, 0-10V corresponds
to 0-100% (1.)
220CH Display signal of ACI analog input terminal, 4-V20mA/0-10V
corresponds to 0-100% (2.)
220DH Display signal of AUI analog input terminal, -10V~10V
corresponds to -100~100% (3.)
220EH Display the IGBT temperature of drive power module in
o
C (c.)
220FH Display the temperature of capacitance in
o
C (i.)
2210H The status of digital input (ON/OFF), refer to Pr.02-12
2211H The status of digital output (ON/OFF), refer to Pr.02-18
2212H Display the multi-step speed that is executing (S)
2213H The corresponding CPU pin status of digital input (d.)
2214H The corresponding CPU pin status of digital output (O.)
2218H Position command tracing error (P.)
2219H Display times of counter overload (0.00~100.00%)
221AH Display GFF in % (G.)
221BH Display DCbus voltage ripples (Unit: Vdc) (r.)
221CH Display PLC register D1043 data (C)
221DH Display Pole of Permanent Magnet Motor
221EH User page displays the value in physical measure
221FH Output Value of Pr.00-05
2222H
Fan speed of the drive
2223H
Control mode of the drive 0: speed mode 1: torque mode
2224H
Carrier frequency of the drive
4. Exception response:
The AC motor drive is expected to return a normal response after receiving command messages
from the master device. The following depicts the conditions when no normal response is replied to