Chapter 11 Description of Parameter Settings
|
C200 Series
11-128
The AC motor drive does not receive the messages due to a communication error; thus, the AC
motor drive has no response. The master device will eventually process a timeout condition.
The AC motor drive receives the messages without a communication error, but cannot handle them.
An exception response will be returned to the master device and an error message “CExx” will be
displayed on the keypad of AC motor drive. The xx of “CExx” is a decimal code equal to the
exception code that is described below.
In the exception response, the most significant bit of the original command code is set to 1, and an
exception code which explains the condition that caused the exception is returned.
Example:
ASCII mode:
RTU mode:
STX ‘:’ Address
01H
‘0’ Function
86H
Address
‘1’ Exception
code
02H
‘8’
CRC CHK Low
C3H
Function
‘6’
CRC CHK High
A1H
‘0’
Exception code
‘2’
‘7’
LRC CHK
‘7’
CR
END
LF
The explanation of exception codes:
Exception
code
Explanation
1
Illegal data value:
The data value received in the command message is not available for the AC drive.
2
Illegal data address:
The data address received in the command message is not available for the AC
motor drive.
3
Parameters are locked: parameters can’t be changed
4
Parameters can’t be changed during operation
10
Communication time-out.
~
Reserved
Response Delay Time
Factory Setting: 2.0
Settings 0.0~200.0ms
This parameter is the response delay time after AC drive receives communication command as
shown in the following.
PC or PLC command
Handling time
of the AC drive
Response Delay Time
Pr.09-09
Response Message
of the AC Drive
RS-485 BUS
Main Frequency of the Communication
Factory Setting: 60.00