Chapter 11 Description of Parameter Settings
|
C200 Series
11-133
5: Single-phase input
A
Reserved
Electrical Gear at Load Side A1
Electrical Gear at Motor Side B1
Electrical Gear at Load Side A2
Electrical Gear at Motor Side B2
Factory Setting: 100
Settings 1~65535
Parameters 10-04 to 10-07 can be used with the multi-function input terminal (set to 48) to switch
to Pr.10-04~10-05 or Pr.10-06~10-07 as shown as follows
ON = A2: B2
OFF=A 1:B 1
MI=48
Driv er
PG
car d
Motor
Gear
B1 or B2
Gear
A1 or A2
gear ratio
load
encoder is us ed
at load side
Treatment for Encoder Feedback Fault
Factory Setting: 2
Settings 0: Warn and keep operating
1: Warn and RAMP to stop
2: Warn and COAST to stop
Detection Time of Encoder Feedback Fault
Factory Setting: 1.0
Settings 0.0~10.0 sec
0: No function
When encoder loss, encoder signal error, pulse signal setting error or signal error, if time exceeds
the detection time for encoder feedback fault (Pr.10-09), the encoder signal error will occur. Refer
to the Pr.10-08 for encoder feedback fault treatment.
Encoder Stall Level
Factory Setting: 115
Settings 0~120%
0: No function
This parameter determines the maximum encoder feedback signal allowed before a fault occurs.