Chapter 13 CANopen Overview
|
C200 Series
13-12
13.4 CANopen Supporting Index
Basic Index Support by C200:
Index
Sub
Definition
Factory Setting
R/W
Size
Note
1000H 0 Device type
00010192H
R U32
1001H 0 Error register
0
R U8
1005H 0 COB-ID SYNC message
80H
R U32
1006H 0 Communication cycle period
0 RW
U32
Unit: us
The setting value should be in a
multiple of 500us (integer)
within the range 500us to 16ms
1008H 0 Manufacturer device name
0
R U32
1009H 0 Manufacturer hardware version
0
R U32
100AH 0 Manufacturer software version
0
R U32
100CH 0 Guarding time
0 RW
U16
Unit: ms
100DH 0 Guarding factor
0 RW
U8
0 Store Parameter
2
R U8
1 Save all parameters
0 RW
U32
1010H
2 Save communication parameter
1 RW
U32
0 Restore Parameter
2
R U8
1 Restore all parameters
0 RW
U32
1011H
2
Restore communication
parameter
1 RW
U32
1014H 0 COB-ID emergency
0Node-ID
R U32
1015H 0 Inhibit time EMCY
0 RW
U16
Unit:100us
The setting value should be in a
multiple of 10 (integer)
0 Consumer heartbeat time
1
R U8
1016H
1 Consumer 1
0 RW
U32
Unit: 1ms
Disable Guarding time to function
properly
1017H 0 Producer heartbeat time
0 RW
U16
Unit: 1ms
Disable Guarding time to function
properly
0 Number
0
R U8
1 Vender ID
000001DDH
R U32
2 Product code
2A00+machine code
R U32
1018H
3 Revision
00010000H
R U32
0 Server SDO Parameter
2
R U8
1 COB-ID Client -> Server
0Node-ID
R U32
1200H
2 COB-ID Client <- Server
0Node-ID
R U32
0 Number
2
R U8
1 COB-ID used by PDO
00Node-ID RW
U32
00:Acyclic& Synchronous
01~240:Cyclic & Synchronous
1400H
2 Transmission Type
5 RW
U8
255:Asynchronous
Call 1(800)985-6929 for Sales