Chapter 13 CANopen Overview
|
C200 Series
13-15
Index
Sub
Definition
Factory Setting
R/W
Size
Note
4 4.Mapped Object
20266310H RW
U32
0 Number
3 RW
U8
1 1.Mapped Object
60410010H RW
U32
2 2.Mapped Object
60640020H RW
U32
3 3.Mapped Object
60610008H RW
U32
1A02H
4 4.Mapped Object
0 RW
U32
0 Number
3 RW
U8
1 1.Mapped Object
60410010H RW
U32
2 2.Mapped Object
60770010H RW
U32
3 3.Mapped Object
60610008H RW
U32
1A03H
4 4.Mapped Object
0 RW
U32
C200 Index:
Parameter index corresponds to each other as following:
Index
sub-Index
2000H + Group 1
For example:
Pr.10.15 (Encoder Slip Error Treatment)
Group
member
10(0
A
H) - 15(0FH)
Index = 2000H + 0AH = 200A
Sub Index = 0FH + 1H = 10H
C200 Control Index:
Delta Standard Mode (Old definition)
Index Sub
Definition
Factory
Setting
R/W Size
Note
0 Number
3
R U8
00B
:
disable
01B
:
stop
10B
:
disable
Bit 0~1
11B
:
JOG Enable
Bit2~3 Reserved
00B
:
disable
01B
:
Direction forward
10B
:
Reverse
Bit4~5
11B
:
Switch Direction
00B
:
1
st
step
acceleration/deceleration
Bit6~7
01B
:
2
nd
step
acceleration/deceleration
1 Control
word
0
RW
U16
Bit8~15 Reserved
2 vl target velocity
(
Hz
)
0
RW
U16
2020H
3 Other
trigger
0
RW
U16
Bit0
1
:
E.F. ON
Call 1(800)985-6929 for Sales
deltaacdrives.com
sales@deltaacdrives.com
Call 1(800)985-6929 for Sales
deltaacdrives.com
sales@deltaacdrives.com