Chapter 13 CANopen Overview
|
C200 Series
13-21
Display
Fault code
Description
CANopen
fault code
CANopen
fault
register
(bit 0~7)
ovS
Ov at stop
Fault
000AH
Over-voltage at stop. Hardware failure in
current detection
3210H
2
LvA
Lv at accel
Fault
000BH
DC BUS voltage is less than Pr.06.00
during acceleration.
3220H
2
Lvd
Lv at decel
Fault
000CH
DC BUS voltage is less than Pr.06.00
during deceleration.
3220H
2
Lvn
Lv at normal SPD
Fault
000DH
DC BUS voltage is less than Pr.06.00 in
constant speed.
3220H
2
LvS
Lv at stop
Fault
000EH
DC BUS voltage is less than Pr.06-00 at
stop
3220H
2
OrP
Phase Lacked
Fault
000FH Phase
Loss
Protection
3130H
2
oH1
IGBT over heat
Fault
0010H
IGBT overheat
IGBT temperature exceeds protection
level.
1~15HP: 90
℃
20~100HP: 100
℃
4310H
3
oH2
Hear Sink oH
Fault
0011H
Heatsink overheat
Heat sink temperature exceeds 90oC
4310H
3
tH1o
Thermo 1 open
Fault
0012H
Temperature detection circuit error
(IGBT)
IGBT NTC
FF00H
3
tH2o
Thermo 2 open
Fault
0013H
Temperature detection circuit error
(capacity module)
CAP NTC
FF01H
3
PWR
Power RST OFF
Fault
0014H
Power RST off
FF02H
2