Chapter 13 CANopen Overview
|
C200 Series
13-25
Display
Fault code
Description
CANopen
fault code
CANopen
fault
register
(bit 0~7)
EoL2
Thermal relay 2
Fault
cE1
Modbus CMD err
Fault
0036H
Illegal function code
7500H
4
Thermal relay 2
Fault
cE2
Modbus ADDR err
Fault
0037H
Illegal data address (00H to 254H)
7500H
4
Thermal relay 2
Fault
cE3
Modbus DATA err
Fault
0038H
Illegal data value
7500H
4
Thermal relay 2
Fault
cE4
Modbus slave FLT
Fault
0039H
Data is written to read-only address
7500H
4
Thermal relay 2
Fault
cE10
Modbus time out
Fault
003AH
Modbus transmission timeout.
7500H
4
Thermal relay 2
Fault
cP10
Keypad time out
Fault
003BH
Keypad transmission timeout.
7500H
4
Thermal relay 2
Fault
bF
Braking fault
Fault
003CH
Brake resistor fault
7110H
4
Thermal relay 2
Fault
ydc
Y-delta connect
Fault
003DH Motor
Y-
Δ
switch error
3330H
2
Thermal relay 2
Fault
dEb
Dec. Energy back
Fault
003EH Energy regeneration when decelerating
3320H
2
Thermal relay 2
Fault
oSL
Over slip Error
Fault
003FH
Overslip error. Slip exceeds Pr.05.26
limit and slip duration exceeds Pr.05.27
setting.
FF00H
7
Thermal relay 2
Fault
ovU
Over volt. Unknow
Fault
Thermal relay 2
Fault
ocU
Unknow Over Apm
Fault
0042H Over current caused by unknown reason
2310H
1