Chapter 14 PLC Function
|
C200 Series
14-26
14.5.4 Communication Address for PLC Devices
Device
Range
Type
Address (Hex)
X 00~17
(Octal)
bit
0400~040F
Y 00~17
(Octal)
bit
0500~050F
T 00~159 bit/word 0600~069F
M 000~799
bit
0800~0B1F
M 1000~1079
bit
0BE8~0C37
C 0~79 bit/word 0E00~0E47
D 00~399
word
1000~118F
D 1000~1099
word
13E8~144B
Function Code
Function Code
Description
Supported Devices
01
Read coil status
Y, M, T, C
02
Read input status
X,Y,M,T,C
03
Read one data
T,C,D
05
Force changing one coil status
Y,M,T,C
06
Write in one data
T,C,D
0F
Force changing multiple coil
status
Y,M,T,C
10
Write in multiple data
T,C,D
Only when PLC is at Stop status, PLC data can be read/write via communication device. When PLC
is at Run status, the communication address should be the mapping address, e.g. for Pr.04-00 it
maps to 0400H.
NOTE
When PLC function is activated, C2000 can Read/Write the PLC and drive’s parameter by different addresses (pre-defined
station number for the AC motor drive is 1, for PLC station number is 2)