Chapter 5 Main Circuit Terminals
|
C200 Series
5-5
Frame A
Main circuit terminals
:
R/L1, S/L2, T/L3, U/T1, V/T2, W/T3,
, DC+(+2,+1), DC-, B1, B2
Models
Max. Wire
Gauge
Min. Wire Gauge
Torque
(±10%)
VFD040CB43A-20/-21/-21M
10 AWG (5.3mm
2
)
VFD055CB43A-20/-21/-21M
10 AWG (5.3mm
2
)
VFD075CB43A-20/-21/-21M
8 AWG
(8.4mm
2
)
8 AWG (8.4mm
2
)
M4
20kg-cm
(17.4 lb-in.)
(1.96Nm)
UL installations must use 600V, 75
℃
or 90
℃
wire. Use copper wire only.
NOTE
Figure 1 shows the terminal specification.
Figure 2 shows the specification of insulated heat shrink tubing that comply with
UL (600V, YDPU2).