Chapter 6 Control Terminals
|
C200 Series
6-3
Wiring precautions:
Reserves 5mm and properly install the wire into the terminal; fasten the installation by a
slotted screwdriver. If the wire is stripped, sort the wire before install into the terminal.
Flathead screwdriver: blade width 3.5mm, tip thickness 0.6mm
In the figure above, the factory setting for S1-SCM is short circuit. The factory setting for
+24V-COM is short circuit and SINK mode (NPN); please refer to Chapter 4 Wiring for more
detail.
Terminals
Terminal Function
Factory Setting (NPN mode)
+24V
Digital control signal common
(Source)
+24V
±
5% 100mA
COM
Digital control signal common
(Sink)
Common for multi-function input terminals
FWD
Forward-Stop command
FWD-DCM:
ON
Î
forward running
OFF
Î
deceleration to stop
REV Reverse-Stop
command
REV-DCM:
ON
Î
reverse running
OFF
Î
deceleration to stop
MI1
~
MI6
Multi-function input 1~6
Refer to parameters 02-01~02-08 to program the
multi-function inputs MI1~MI8.
ON: the activation current is 6.5mA 11Vdc
≧
OFF: leakage current tolerance is 10
μ
A 11Vdc
≦
MI7
~
MI8
Multi-function input 7~8
It can be a multi input option for Pr02-01 ~ 02-08. It
can also be used as a PG function. For more
information on PG function, see page 6-5.
RA1
Multi-function relay output 1
(N.O.) a
RB1
Multi-function relay output 1
(N.C.) b
RC1
Multi-function relay common 1
RA2
Multi-function relay output 2
(N.O.) a
RC2
Multi-function relay common 2
Resistive Load:
5A(N.O.)/3A(N.C.) 250VAC
5A(N.O.)/3A(N.C.) 30VDC
Inductive Load (COS 0.4):
2.0A(N.O.)/1.2A(N.C.) 250VAC
2.0A(N.O.)/1.2A(N.C.) 30VDC
It is used to output each monitor signal, such as drive
is in operation, frequency attained or overload
indication.
DFM1
Digital frequency meter 1
(when Pr.02-21=0, DFM1 is the setting of
Pr.02-16)
(When Pr.02-21
≧
1, DM1 is the pulse output.)
DFM2
Digital frequency meter 2
(When Pr.02-55 = 0, DFM2 is the setting value
of Pr.02-17.)
(When Pr.02-55
≧
1, DFM2 is the pulse output)
DCM
Digital frequency signal common
The AC motor drive releases various monitor signals,
such as drive in operation, frequency attained and
overload indication, via transistor (open collector).
Regard the pulse voltage as the output monitor signal
Duty-cycle: 50%
Min. load impedance: 1k
Ω
/100pf
Max. current: 30mA
Max. voltage: 30Vdc
DFM1
30V/30mA 33kHz
DFM2
DCM
Multi-function output
frequency terminals
SG+
SG-
Modbus RS-485
8
1
PIN4
、
PIN5 equals to the PIN4, PIN5 of the RJ45
internet cable connector.
PIN 3: GND
PIN 4: SG-
PIN 5: SG+