Chapter 7 Optional Accessories
|
C200 Series
7-7
Correct wiring:
M1
M2
Mn
reactor
AC motor drive
AC motor drive
AC motor drive
motor
motor
motor
Application 2
Silicon rectifier and AC motor drive are connected to the same power.
Problem: Switching spikes will be generated when the silicon rectifier switches ON/OFF.
These spikes may damage the mains circuit.
Correct wiring:
DC
power
reactor
reactor
AC motor drive
motor
silicon rectifier
Application 3
When the power supply capacity exceeds 10 times of the inverter capacity.
Problem: When the mains power capacity is too large, line impedance will be small and the
charge current will be too high. This may damage AC motor drive due to higher
rectifier temperature.
Correct wiring
large-capacity
power
reactor
small-capacity
AC motor drive
motor
DC Reactor
460V DC Choke
Input Voltage
kW
HP
DC Amps
Inductance (mh)
4 5.5 23 2.7
5.5 7.5 25 2.47
460Vac 50/60Hz
3-Phase
7.5 10 30 2.1