Chapter 8 Specification
|
C200 Series
8-1
Chapter
08 Specification
230V Series -1 Phase
Frame Size
A0
Model VFD -_ _ _CB21A-
_ _ _
*1
004 007 015 022
Applicable Motor Output (kW)
0.4 0.75 1.5 2.2
Applicable Motor Output (HP)
0.5 1 2 3
Rated Output Capacity (kVA)
1.2
2.0
3.2
4.4
Rated Output Current (A)
3
5
8
11
Overload Tolerance
rated output current is 120% for 60 seconds;
rated output current is 160% for 3 seconds
Max. Output Frequency (Hz)
600.00Hz
NORMAL
DUTY
Carrier Frequency (kHz)
2~15kHz (Factory Setting: 8 kHz)
Rated Output Capacity (kVA)
1.1
1.9
2.8
4.0
Rated Output Current (A)
2.8
4.8
7.1
10
Overload Tolerance
rated output current is 150% for 60 seconds;
rated output current is 180% for 3 seconds
Max. Output Frequency (Hz)
600.00Hz
O
u
tput Rat
ing
HEA
V
Y
DUTY
Carrier Frequency (kHz)
2~15kHz (Factory Setting: 2 kHz)
Input Current (A) Normal Duty
7.2 12 15.7 22
Input Current (A) Heavy Duty
6.7
11.5
14
20
Rated Voltage/Frequency
AC 200V~240V (-15% ~ +10%), 50/60Hz, 1-Phase
Operating Voltage Range
170~265Vac
Input
Rati
ng
Frequency Tolerance
47~63Hz
Cooling method
Natural cooling
Fan cooling
Braking Chopper
Built-in
230V Series -3 Phase
Frame Size
A0
Model VFD -_ _ _CB23A-
_ _ _
*1
004 007 015 022 037
Applicable Motor Output (kW)
0.4 0.75 1.5 2.2 3.7
Applicable Motor Output (HP)
0.5 1 2 3 5
Rated Output Capacity (kVA)
1.2
2.0
3.2
4.4
6.8
Rated Output Current (A)
3
5
8
11
17
Overload Tolerance
rated output current is 120% for 60 seconds;
rated output current is 160% for 3 seconds
Max. Output Frequency (Hz)
600.00Hz
NORMAL
DUTY
Carrier Frequency (kHz)
2~15kHz (Factory Setting: 8 kHz)
Rated Output Capacity (kVA)
1.1
1.9
2.8
4.0
6.4
Rated Output Current (A)
2.8
4.8
7.1
10
16
Overload Tolerance
rated output current is 150% for 60 seconds;
rated output current is 180% for 3 seconds
Max. Output Frequency (Hz)
600.00Hz
O
u
tput Rat
ing
HEA
V
Y
DUTY
Carrier Frequency (kHz)
2~15kHz (Factory Setting: 2 kHz)
Input Current (A) Normal Duty
3.9 6.4 12 16 20
Input Current (A) Heavy Duty
3.6
6.1
11
15
18.5
Rated Voltage/Frequency
AC 200V~240V (-15% ~ +10%), 50/60Hz 3-Phase
Operating Voltage Range
170~265Vac
Input
Rati
ng
Frequency Tolerance
47~63Hz
Cooling method
Natural cooling
Fan cooling
Braking Chopper
Built-in