Chapter 10 Summary of Parameter Settings
|
C200 Series
10-6
Parameter
Explanation
Settings
Factory
Setting
01-30
Skip Frequency 2 (upper limit)
0.00~600.00Hz 0.00
01-31
Skip Frequency 2 (lower limit)
0.00~600.00Hz 0.00
01-32
Skip Frequency 3 (upper limit)
0.00~600.00Hz 0.00
01-33
Skip Frequency 3 (lower limit)
0.00~600.00Hz 0.00
01-34 Zero-speed
Mode
0: Output waiting
1: Zero-speed operation
2: Fmin (the 4
th
output frequency)
0
01-35
Output Frequency of Motor 2
0.00~600.00Hz
60.00/
50.00
01-36
Output Voltage of Motor 2
230V: 0.0V~255.0V
460V: 0.0V~510.0V
200.0
400.0
01-37
Mid-point Frequency 1 of
Motor 2
0.00~600.00Hz 3.00
01-38
Mid-point Voltage 1 of Motor 2
230V: 0.0V~240.0V
460V: 0.0V~480.0V
11.0
22.0
01-39
Mid-point Frequency 2 of
Motor 2
0.00~600.00Hz 0.50
01-40
Mid-point Voltage 2 of Motor 2
230V: 0.0V~240.0V
460V: 0.0V~480.0V
2.0
4.0
01-41
Min. Output Frequency of
Motor 2
0.00~600.00Hz 0.00
01-42
Min. Output Voltage of Motor 2
230V: 0.0V~240.0V
460V: 0.0V~480.0V
0.0
0.0
01-43
V/f Curve Selection
0: V/f curve determined by Pr.01-00~Pr.01-08
1: Curve to the power of 1.5
2: Curve to the power of 2
0
01-44
Optimal
Acceleration/Deceleration
Setting
0: Linear accel. /decel.
1: Auto accel.; linear decel.
2: Linear accel.; auto decel.
3: Auto accel./decel.
4: Linear, stall prevention by auto accel./decel. (limit
by Pr.01-12 to 01-21)
0
01-45
Time Unit for Accel. /Decel.
and S Curve
0: Unit: 0.01 sec
1: Unit: 0.1sec
0
01-46
CANopen Quick Stop Time
Pr. 01-45=0: 0.00~600.00 sec
Pr. 01-45=1: 0.0~6000.0 sec
1.00