Chapter 10 Summary of Parameter Settings
|
C200 Series
10-8
Parameter
Explanation
Settings
Factory
Setting
50: Master dEb action input
51: Selection for PLC mode bit0
52: Selection for PLC mode bit1
53: Trigger CANopen quick stop
54~55:
Reserved
56: Local/Remote Selection
02-09 UP/DOWN
key
mode
0: up/down by the accel. /decel. time
1: up/down constant speed (Pr.02-10)
0
02-10
Constant speed. The
Accel. /Decel. Speed of the
UP/DOWN Key
0.01~1.00Hz/ms
0.01
02-11
Digital Input Response
Time
0.000~30.000 second
0.005
02-12
Digital Input Mode
Selection
0000h~FFFFh (0: N.O.; 1: N.C.
)
0000
02-13
Multi-function Output 1
RY1
0: No function
11
02-14
Multi-function Output 2
RY2
1: Operation Indication
1
02-16
Multi-function Output 3
(MO1)
(When Pr02-21 =0, this
parameter is enabled.)
2: Operation speed attained
0
02-17
Multi-function Output 4
(MO2)
(When Pr02-55 =0, this
parameter is enabled.)
3: Desired frequency attained 1 (Pr.02-22)
0
4: Desired frequency attained 2 (Pr.02-24)
0
5: Zero speed (Frequency command)
0
6: Zero speed, include STOP(Frequency command)
0
7: Over torque 1(Pr.06-06~06-08)
0
8: Over torque 2(Pr.06-09~06-11)
0
9: Drive is ready
0
10: Low voltage warning
(
LV
)
(Pr.06-00)
0
11: Malfunction indication
0
12: Mechanical brake release(Pr.02-32)
0
13: Overheat warning (Pr.06-15)
0
14: Software brake signal indication(Pr.07-00)
0
15: PID feedback error
16: Slip error (oSL)
17: Terminal count value attained, does not return to 0
(Pr.02-20)
18: Preliminary count value attained, returns to 0
(Pr.02-19)
19: Base Block
20:
Warning
output
21: Over voltage warning
22: Over-current stall prevention warning
23: Over-voltage stall prevention warning
24: Operation mode indication
25: Forward command
26: Reverse command
27: Output when current >= Pr.02-33 (>= 02-33)
28: Output when current <=Pr.02-33 (<= 02-33)
29: Output when frequency >= Pr.02-34 (>= 02-34)