Chapter 10 Summary of Parameter Settings
|
C200 Series
10-17
Parameter
Explanation
Settings
Factory
Setting
Motor
05-26
Accumulative
Watt-second of Motor in
Low Word (W-sec)
Read only
#.#
05-27
Accumulative
Watt-second of Motor in
High Word (W-sec)
Read only
#.#
05-28
Accumulative Watt-hour of
Motor (W-Hour)
Read only
#.#
05-29
Accumulative Watt-hour of
Motor in Low Word
(KW-Hour)
Read only
#.#
05-30
Accumulative Watt-hour of
Motor in High Word
(KW-Hour)
Read only
#.#
05-31
Accumulative Motor
Operation Time (Min)
00~1439
0
05-32
Accumulative Motor
Operation Time (day)
00~65535
0
05-33
Induction Motor and
Permanent Magnet Motor
Selection
0: Induction Motor
1: Permanent Magnet Motor
0
05-34
Full-load current of
Permanent Magnet Motor
0.00~655.35Amps
0.00
05-35
Rated Power of
Permanent Magnet Motor
0.00~655.35kW
0.00
05-36
Rated speed of
Permanent Magnet Motor
0~65535rpm
2000
05-37
Pole number of
Permanent Magnet Motor
0~65535
10
05-38
Inertia of Permanent
Magnet Motor
0.0~6553.5 kg.cm
2
0.0
05-39
Stator Resistance of PM
Motor
0.000~65.535
Ω
0.000
05-40
Permanent Magnet Motor
Ld
0.00~655.35mH
0.000
05-41
Permanent Magnet Motor
Lq
0.00~655.35mH
0.000
05-42
PG Offset angle of PM
Motor
0.0~360.0°
0.0
05-43
Ke parameter of PM Motor 0~65535 (Unit: V/1000rpm)
0
Call 1(800)985-6929 for Sales
deltaacdrives.com
sales@deltaacdrives.com
Call 1(800)985-6929 for Sales
deltaacdrives.com