Chapter 10 Summary of Parameter Settings
|
C200 Series
10-20
Parameter
Explanation
Settings
Factory
Setting
57: Communication error (CE4)
58: Communication Time-out (CE10)
59:
Reserved
60: Brake transistor error (bF)
61:
Y-connection/
△
-connection switch error (ydc)
62: Decel. Energy Backup Error (dEb)
63: Slip error (oSL)
64: Electromagnet switch error (ryF)
65 : PG Card Error (PGF5)
66-78:
Reserved
79: U phase over current (Uocc)
80: V phase over current (Vocc)
81: W phase over current (Wocc)
82: U phase output phase loss (OPHL)
83: V phase output phase loss (OPHL)
84: W phase output phase loss (OPHL)
85~100:
Reserved
101: CANopen software disconnect1 (CGdE)
102: CAN open software disconnect2 (CHbE)
103: CANopen synchronous error (CSYE)
104: CANopen hardware disconnect (CbFE)
105: CANopen index setting error (CIdE)
106: CANopen slave station number setting error
(CAdE)
107: CANopen index setting exceed limit (CFrE)
111: Internal communication overtime error(InrCOM)
06-23
Fault Output Option 1
0~65535(refer to bit table for fault code)
0
06-24
Fault Output Option 2
0~65535(refer to bit table for fault code)
0
06-25
Fault Output Option 3
0~65535(refer to bit table for fault code)
0
06-26
Fault Output Option 4
0~65535(refer to bit table for fault code)
0
06-27
Electronic Thermal Relay
Selection 2 (Motor 2)
0: Inverter motor
1: Standard motor
2: Disable
2
06-28
Electronic Thermal
Characteristic for Motor 2
30.0~600.0 sec
60.0
06-29
PTC Detection Selection
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
0
06-30 PTC
Level
0.0
~
100.0%
50.0
06-31
Frequency Command for
Malfunction
0.00~655.35 Hz
Read
only
06-32
Output Frequency at
Malfunction
0.00~655.35 Hz
Read
only
06-33
Output Voltage at
Malfunction
0.0~6553.5 V
Read
only
06-34
DC Voltage at Malfunction
0.0~6553.5 V
Read
only
06-35
Output Current at
Malfunction
0.00~655.35 Amp
Read
only
06-36
IGBT Temperature at
Malfunction
0.0~6553.5
℃
Read
only
06-37
Capacitance Temperature
at Malfunction
0.0~6553.5
℃
Read
only
06-38
Motor Speed in rpm at
Malfunction
0~65535
Read
only
06-39
Torque Command at
Malfunction
0~65535
Read
only
Call 1(800)985-6929 for Sales
deltaacdrives.com
sales@deltaacdrives.com
Call 1(800)985-6929 for Sales
deltaacdrives.com
sales@deltaacdrives.com