Chapter 10 Summary of Parameter Settings
|
C200 Series
10-21
Parameter
Explanation
Settings
Factory
Setting
06-40
Status of Multi-function
Input Terminal at
Malfunction
0000h~FFFFh
Read
only
06-41
Status of Multi-function
Output Terminal at
Malfunction
0000h~FFFFh
Read
only
06-42
Drive Status at
Malfunction
0000h~FFFFh
Read
only
06-43 Reserved
06-44 Reserved
06-45
Treatment to Output
Phase Loss Detection
(OPHL)
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
3
06-46
Deceleration Time of
Output Phase Loss
0.000~65.535 sec
0.500
06-47 Current
Bandwidth
0.00~655.35%
1.00
06-48
DC Brake Time of Output
Phase Loss
0.000~65.535sec 0.000
06-49 Reserved
06-50
Time for Input Phase Loss
Detection
0.00~600.00 sec.
0.20
06-51 Reserved
06-52
Ripple of Input Phase
Loss
230V model: 0.0~160.0 Vdc
460V model: 0.0~320.0 Vdc
30.0
/60.0
06-53
Treatment for the detected
Input Phase Loss (OrP)
0: warn and ramp to stop
1: warn and coast to stop
0
06-54 Reserved
06-55 Derating
Protection
0: constant rated current and limit carrier wave by load
current and temperature
1: constant carrier frequency and limit load current by
setting carrier wave
2: constant rated current(same as setting 0), but close
current limit
0
06-56
~
06-59
Reserved
06-60
Software Detection GFF
Current Level
0.0~6553.5 %
60.0
06-61
Software Detection GFF
Filter Time
0.0~6553.5 %
0.10
06-62
Disable Level of dEb
230V series: 0.0~220.0 Vdc
460V series: 0.0~440.0 Vdc
180.0
/360.0
06-63
Fault Record 1 (Min)
0~64799 min
Read
only
06-64
Fault Record 2 (Min)
0~64799 min
Read
only
06-65
Fault Record 3 (Min)
0~64799 min
Read
only
06-66
Fault Record 4 (Min)
0~64799 min
Read
only
06-67
Fault Record 5 (Min)
0~64799 min
Read
only
06-68
Fault Record 6 (Min)
0~64799 min
Read
only
06-69
Days of operation
Read only
Read
only