Chapter 10 Summary of Parameter Settings
|
C200 Series
10-24
Parameter
Explanation
Settings
Factory
Setting
07-22 Energy-saving
Gain
10
~
1000%
100
07-23
Auto Voltage
Regulation(AVR) Function
0: Enable AVR
1: Disable AVR
2: Disable AVR during deceleration
0
07-24
Filter Time of Torque
Command (V/F and SVC
control mode)
0.001~10.000 sec
0.020
07-25
Filter Time of Slip
Compensation (V/F and
SVC control mode)
0.001~10.000 sec
0.100
07-26
Torque Compensation
Gain (V/F and SVC control
mode)
0~10 0
07-27
Slip Compensation Gain
(V/F and SVC control
mode)
0.00~10.00 0.00
07-28 Reserved
07-29
Slip Deviation Level
0.0~100.0%
0: No detection
0
07-30
Detection Time of Slip
Deviation
0.0~10.0 sec
1.0
07-31 Over
Slip
Treatment
0: Warn and keep operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning
0
07-32
Motor Hunting Gain
0~10000
1000
07-33
Auto Reset Time for
Restart after Fault
0.0~6000.0 sec
60.0
Call 1(800)985-6929 for Sales
deltaacdrives.com
sales@deltaacdrives.com
Call 1(800)985-6929 for Sales
deltaacdrives.com
sales@deltaacdrives.com