Chapter 10 Summary of Parameter Settings
|
C200 Series
10-26
09 Communication Parameters
Parameter
Explanation
Settings
Factory
Setting
09-00
COM1 Communication
Address
1~254 1
09-01
COM1 Transmission
Speed
4.8~115.2Kbps 19.2
09-02
COM1 Transmission Fault
Treatment
0: Warn and continue operation
1: Warn and ramp to stop
2: Warn and coast to stop
3: No warning and continue operation
3
09-03
COM1 Time-out Detection
0.0~100.0 sec.
0.0
09-04
COM1 Communication
Protocol
0: 7N1 (ASCII)
1: 7N2 (ASCII)
2: 7E1 (ASCII)
3: 7O1 (ASCII)
4: 7E2 (ASCII)
5: 7O2 (ASCII)
6: 8N1 (ASCII)
7: 8N2 (ASCII)
8: 8E1 (ASCII)
9: 8O1 (ASCII)
10: 8E2 (ASCII)
11: 8O2 (ASCII)
12: 8N1 (RTU)
13: 8N2 (RTU)
14: 8E1 (RTU)
15: 8O1 (RTU)
16: 8E2 (RTU)
17: 8O2 (RTU)
13
09-05
~
09-08
Reserved
09-09 Response
Delay
Time 0.0~200.0ms
2.0
09-10
Main Frequency of the
Communication
0.00~600.00Hz 60.00
09-11 Block
Transfer
1
0~65535
0
09-12 Block
Transfer
2
0~65535
0
09-13 Block
Transfer
3
0~65535
0
09-14 Block
Transfer
4
0~65535
0
09-15 Block
Transfer
5
0~65535
0
09-16 Block
Transfer
6
0~65535
0
09-17 Block
Transfer
7
0~65535
0
09-18 Block
Transfer
8
0~65535
0
09-19 Block
Transfer
9
0~65535
0
09-20 Block
Transfer
10
0~65535
0
09-21 Block
Transfer
11
0~65535
0
09-22 Block
Transfer
12
0~65535
0
09-23 Block
Transfer
13
0~65535
0
09-24 Block
Transfer
14
0~65535
0
09-25 Block
Transfer
15
0~65535
0
09-26 Block
Transfer
16
0~65535
0
Call 1(800)985-6929 for Sales