Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual
42
2. After the
Factory Setting
box is selected, a confirmation window will appear. Click on
Yes
to return to default
settings (in approx. 5~10 seconds), and the password will be cleared as well.
3. After the searching, all the parameters have already returned to their default settings.
6.5 IP Filter Protection
Application
Setting the IP filter protection
Network
environment
(1) IP address of DVPEN01-SL: 192.168.0.4
(2) Only connections to 192.168.0.7 and 172.16.0.1~172.16.0.255 are allowed.
1. See 6.1 for the connection and how to set the communication.
2. Open the setup page and switch to the
IP Filter
page.