47
4. After all the settings in DVPEN01-SL are completed, compile the ladder diagram in the MPU and download it to
the MPU. See below for the program design:
END
X0
T0
K100
K3
K1
K4
K5
K6
K1
X0
T0
K100
K1
K1
T0
K100
K1
K1
T0
K100
K1
K1
Y0
Y0
Explanations:
•
If the rising-edge of X0 is triggered, X0 will go from Off to On. Write “1” into CR#3 of DVPEN01-SL, and the
first E-mail will be sent out.
•
If the falling-edge of X0 is triggered, X0 will go from On to Off. Write “1” into CR#4 of DVPEN01-SL, and the
second E-mail will be sent out.
•
If the rising-edge of Y0 is triggered, Y0 will go from Off to On. Write “1” into CR#5 of DVPEN01-SL, and the
third E-mail will be sent out.
•
If the falling-edge of Y0 is triggered, Y0 will go from On to Off. Write “1” into CR#6 of DVPEN01-SL, and the
fourth E-mail will be sent out.
•
6.8 Application of Data Exchange (1)
Application
Writing the time in RTC in PLC_B into D0~D6 of PLC_A
Network
environment
(1) Adopt a static IP address.
(2) IP address of PLC_A: 192.168.0.4
(3) IP address of PLC_B: 192.168.0.5
(4) Update from PLC_B to PLC_A.
1. See 6.1 for how to set the communication.