Thank you for choosing DVPEN01-SL module. To correctly install and operate DVPEN01-SL, please read the manual
carefully before using the module.
DVPEN01-SL is an Ethernet communication module for remote setting and communication through WPLSoft.
DVPEN01-SL is able to send E-mails, automatically correct the RTC in DVP28SV11R/T and exchange data. It supports
MODBUS TCP communication protocol and can conduct remote monitoring by using SCADA (Supervisor Control and
Data Acquisition) software or HMI (Human Machine Interfaces). DVPEN01-SL can be the master of MODBUS TCP,
sending out MODBUS TCP instructions and controlling the peripheral equipment. In addition, under MDI/MDI-X
auto-detection, it does not need to use a crossing cable. See the contents below for more detailed instructions on
DVPEN01-SL module.
1.1 Functions
Auto-detects 10/100Mbps transmission speed
MDI/MDI-X auto-detection
Supports MODBUS TCP protocol (at the same time supports Master and Slave mode)
Able to send out E-mails
Auto-corrects the RTC in PLC through the Internet time correction function
Supports point-to-point data exchange (Max. data exchange length: 200 bytes)
1.2 Specifications
Internet interface
Item
Specification
Interface
RJ-45 with Auto MDI/MDIX
Number of ports
1 Port
Transmission method
IEEE802.3, IEEE802.3u
Transmission cable
Category 5e / UC-PRG030-20A (3M)
Transmission speed
10/100 Mbps Auto-Detect
Network protocol
ICMP, IP, TCP, UDP, DHCP, SMTP, NTP, MODBUS TCP, SNMP
Serial communication interface
Item
Specification
Interface
RS-232
Number of ports
1 Port
Transmission cable
UC-MS030-01A (3M) / UC-MS010-02A (1M) / UC-PRG020-12A (2M)
Environment
Item
Specification
Noise immunity
ESD (IEC 61131-2, IEC 61000-4-2): 8KV Air Discharge
EFT (IEC 61131-2, IEC 61000-4-4): Power Line: 2KV
Analog & Communication I/O: 1KV
Damped-Oscillatory Wave: Power Line: 1KV
RS (IEC 61131-2, IEC 61000-4-3): 26MHz~1GHz, 10V/m
Environment
Operation: 0°C~55°C (temperature), 5~95% (humidity), Pollution degree 2;
Storage: -25°C~70°C (temperature), 5~95% (humidity)
Vibration/ Shock
Resistance
Standard: IEC61131-2, IEC 68-2-6 (TEST Fc)/IEC61131-2 & IEC 68-2-27
(TEST Ea)