Ethernet Communication Module DVPEN01-SL
DVP-PLC Operation Manual
51
6.10 Application of Data Exchange (3)
Firmware version 2.0 and above support this function.
Application
Enable a timer (X20) and write the timer values into D0~D99. Control the program (X21) and write the
present values in D0~D99 of PLC_A into D0~D99 of PLC_B, and write the values in D0~D99 of
PLC-B into D200~D299 of PLC_A. Control the program (X21) to stop the execution.
Network
environment
(1) Adopt a static IP address.
(2) IP address of PLC_A: 192.168.1.99
(3) IP address of PLC_B: 192.168.1.97
(4) Update from PLC_A to PLC_B and PLC_B to PLC_A.
1. See 6.1 for how to set the communication.
2. Open the setup page of PLC_A and switch to the
Data Exchange
page.
3. Select the
Enable Data Exchange
checkbox. Select
Program Control
in the
Enable Condition
drop-down list
box. Check the
Enable
cell corresponding to station address 1.Enter the IP address of PLC_B “192.168.1.97” in
the
IP Address
cell corresponding to station address 1, select D200 and D0 in the
Master Device
cell
corresponding to station address 1, select D0 and D0 in the
Slave Device
cell corresponding to station address
1, and select 100 and 100 in the
Quantity
cell corresponding to station address 1.