Chapter 3 Introduction to Functions
3-27
_3
Description
Default
Set up the data bits for the serial port.
Transparent mode:
7, 8
Modbus RTU:
8
8
Stop Bits
Set up the stop bits for the serial port. Options are 1
and 2.
1
Parity Bits
Set up the parity bits for the serial port. Options are
None, Odd and Even.
None
Modbus ID
Set up the MODBUS ID. The value is between 1 and 247.
1
Modbus Mode
Set up the communication mode for the device. The Device supports ModBus
RTU and ModBus ASCII.
ModBus RTU
Modbus Timeout
Set up the timeout timer from 200ms to 5000ms. If the set value is out of range,
it will be automatically changed to its maximum or minimum value.
1000ms
Master Mode
Scan Interval
Set up the time for scan interval, ranging from 20ms to
60000ms.
30000ms
Read/Write
Set up the access permissions for the mapped register
address;
Read-only:
The device regular read data from
appointed registers in the slave, but will not
update the data to the slave
Write-only:
The device update the data to the
slave when the registers values was changed,
but will not read the data from the slave
Read/write:
The device regular read data from
appointed registers in the slave, will update the
data to the slave when the registers values is
changed.
Read/Write
Slave ID
Set up the corresponding slave communication port.
The value is between 1 and 247.
N/A
Controller
Device types:
Delta PLC:
Use this option for Delta DVP / AH /
Delta DVP
PLC
Summary of Contents for DX-3001 Series
Page 21: ...Chapter 2 Introduction to User Interface 2 9 2_ 4 Cellular setting page ...
Page 44: ...Chapter 3 Introduction to Functions 3 19 _3 ...
Page 45: ...DX 3001 Series Industrial Cloud Router 3 20 _3 ...
Page 49: ...DX 3001 Series Industrial Cloud Router 3 24 _3 ...
Page 50: ...Chapter 3 Introduction to Functions 3 25 _3 ...
Page 115: ...CH5 Introduction to IOT DIACloud 5 25 _5 ...
Page 123: ...DX 3001 Series Industrial Cloud Router 6 8 _6 ...