Chapter 3 Introduction to Functions
3-31
_3
Description
Default
Response Timeout
Set up the timeout timer from 50ms to 100000ms.
If the set value is out of range, it will be
automatically changed to its maximum or minimum
value. The default is 300ms.
300
Scan Interval
Set up the time for scan interval, ranging from
20ms to 60000ms; the default is 3000ms.
30000
Add Mappings
Read/Write
Set up the access permissions for the mapped
register address;
Read-only:
The device regular read data from
appointed registers in the slave, but will not
update the data to the slave
Write-only:
The device update the data to the
slave when the registers values was
changed, but will not read the data from the
slave
Read/write:
The device regular read data
from appointed registers in the slave, will
update the data to the slave when the
registers values is changed.
Read/Write
Slave ID
Set up the corresponding slave communication
port. The value is between 1 and 247.
N/A
Controller
Device types:
Delta PLC:
Delta DVP / AH / AS series PLCs
use this option.
Other:
Use this option for non-Delta DVP / AH
/ AS series PLCs.
Delta DVP PLC
Address Type
Depending on the selected controller type change:
Delta PLC:
The address type is "D"
Other:
The address type is "W"
D
Slave Starting Address
Set up the slave starting address for read/write the
registers in a PLC.
Delta PLC:
Enter the internal D register
number. If you need to read / write D0,
please enter 0 here.
N/A
Summary of Contents for DX-3001 Series
Page 21: ...Chapter 2 Introduction to User Interface 2 9 2_ 4 Cellular setting page ...
Page 44: ...Chapter 3 Introduction to Functions 3 19 _3 ...
Page 45: ...DX 3001 Series Industrial Cloud Router 3 20 _3 ...
Page 49: ...DX 3001 Series Industrial Cloud Router 3 24 _3 ...
Page 50: ...Chapter 3 Introduction to Functions 3 25 _3 ...
Page 115: ...CH5 Introduction to IOT DIACloud 5 25 _5 ...
Page 123: ...DX 3001 Series Industrial Cloud Router 6 8 _6 ...