Force-GT DIN Rail Power Supply
24 V 960 W 3 Phase / DRF-24V960W3GBA
TECHNICAL DATASHEET
All parameters are specified at 25°C ambient and AC input
3x unless otherwise indicated.
www.DeltaPSU.com (May 2022, Rev. 00)
5
EMC
*8
Emissions (CE & RE)
Generic Standards: EN/BS EN 61000-6-3,
CISPR 32, EN/BS EN 55032, FCC Title 47: Class B
Component Power Supply for General Use
EN/BS EN 61204-3
Immunity
Generic Standards: EN/BS EN 55024, EN/BS EN 55035,
EN/BS EN 61000-6-1
Electrostatic Discharge
IEC 61000-4-2 Level 4 Criteria A
1)
Air Discharge: 15 kV
Contact Discharge: 8 kV
Radiated Field
IEC 61000-4-3 Level 3 Criteria A
1)
80 MHz – 1GHz, 10 V/M, 80% Modulation (1 kHz)
1.4 GHz – 2GHz, 10 V/M, 80% Modulation (1 kHz)
2 GHz – 6GHz, 10 V/M, 80% Modulation (1 kHz)
Electrical Fast Transient / Burst
IEC 61000-4-4 Level 4 Criteria A
1)
4 kV
Surge
IEC 61000-4-5 Level 4 Criteria A
1)
Common Mode
3)
: 4 kV
Differential Mode
4)
: 2 kV
Conducted
IEC 61000-4-6 Level 3 Criteria A
1)
150 kHz – 80 MHz, 10 Vrms
Power Frequency Magnetic Fields
IEC 61000-4-8 Level 4 Criteria A
1)
30 A/m
Voltage Dips and Interruptions
IEC 61000-4-11 0% of 3 x 380 Vac
0% of 3 x 480 Vac
0 Vac, 20 ms
0 Vac, 20 ms
Criteria A
1)
Criteria A
1)
40% of 2 x 380 Vac
40% of 2 x 480 Vac
70% of 2 x 380 Vac
70% of 2 x 480 Vac
0%
152 Vac, 200 ms
192 Vac, 200 ms
266 Vac, 500 ms
336 Vac, 500 ms
0 Vac, 5,000 ms
Criteria A
1)
Criteria A
1)
Criteria A
1)
Criteria A
1)
Criteria B
2)
Low Energy Pulse Test
(Ring Wave)
IEC 61000-4-12 Level 3 Criteria A
1)
Common Mode
3)
: 2 kV
Differential Mode
4)
: 1 kV
Harmonic Current Emission
IEC/EN/BS EN 61000-3-2, Class A
Voltage Fluctuation and Flicker
IEC/EN/BS EN 61000-3-3
Voltage Sag Immunity
SEMI F47 – 0706
80% of 380 Vac
70% of 380 Vac
50% of 380 Vac
304 Vac, 1,000 ms
266 Vac, 500 ms
190 Vac, 200 ms
Criteria A
1)
Criteria A
1)
Criteria A
1)
1) Criteria A: Normal performance within the specification limits
2) Criteria B: Temporary degradation or loss of function which is self-recoverable
3) Asymmetrical: Common mode (Line to earth)
4) Symmetrical: Differential mode (Line to line)
*8 Power supply is considered a component in the end-user’s system. Please contact our local sales to get more information about the power supply EMC test setup.