Chapter 4 System Configurations
4-3
Configuring via Telnet
Step 1 Use a CAT5 network cable to connect the SNMP IPv6’s Network port to
the network.
Step 2 Connect the workstation (Windows or Linux) to the LAN that the SNMP
IPv6 is connected to.
Step 3 For Windows, launch DOS prompt mode (Start
→
Run
→
key in cmd
and press Enter). For Linux, launch Shell.
Step 4 Enter the following command: telnet InsightPower or telnet IP address
to initiate telnet connection with the SNMP IPv6.
Step 5 When connection is established, enter Administrator’s account and
password (default: admin/ password, case sensitive). The Main Menu will
appear on the screen. Please refer to
4-5 Configuring via Text Mode
for
more information.
NOTE
1. The SNMP IPv6 terminates idle connections after 60 seconds.
2. Refer to
Chapter 5: InsightPower SNMP IPv6 for UPS Web
for complete
configurations.
4-4
Configuring through COM Port
If a network connection is not available at your location, you can still set up the
SNMP IPv6 via COM port connection. Please follow the instructions below:
NOTE
If you are running a non-Windows system, refer to your system’s user manual
for Telnet clients.
Step 1 Use the provided RJ45 to DB9 cable to connect the SNMP IPv6’s COM port
to the workstations’ COM port.
Step 2 Make sure the two DIP switches of the SNMP IPv6 are set to the OFF posi-
tion (Normal Mode).