InsightPower SNMP IPv6 for UPS
z
z
Smart Shutdown
The Smart Shutdown configuration is used to safely shutdown all of the
connected computers and the UPS. First of all, you should estimate the lon-
gest OS Shutdown Delay time for your operating systems that have been in-
stalled shutdown software and connected to the SNMP IPv6. The SNMP IPv6
will delay the assigned OS Shutdown Delay time and wait for all operating
systems’ shutdown. After that, the SNMP IPv6 will send the assigned UPS
shutdown-delay command to the UPS and turn off the UPS.
z
z
Battery Replacement Date
After you set up battery replacement dates, the SNMP IPv6 will send the
command to the UPS and save the information in the UPS.
z
z
External Battery Pack
After you click Submit to confirm your external battery pack setup, the
SNMP IPv6 will send the command to the UPS and save the external battery
pack quantity in the UPS.
z
z
Bypass Transfer Frequency
After you set a tolerance of bypass transfer frequency and confirm your set-
up, the SNMP IPv6 will send the command to the UPS. If the UPS transfers to
bypass mode and the bypass frequency is out of the tolerance, output will
be turned off and critical loads will be protected.
z
z
Bypass Transfer Voltage
After you set a tolerance of bypass transfer voltage and confirm your setup,
the SNMP IPv6 will send the command to the UPS. If the UPS transfers to
bypass mode and the bypass voltage is out of the tolerance, output will be
turned off and critical loads will be protected.
z
z
Periodic Auto Test
This configuration is used to set up battery test time. After you confirm your
setup, the SNMP IPv6 will send the command to the UPS and save the setup
in the UPS. When the test time is due, the UPS will automatically perform
the battery test.
z
z
Output Dry Contacts
After you click Submit to confirm your setup of output dry contacts, the
SNMP IPv6 will send the command to the UPS, save the values in the UPS,
and report the current UPS’s status.