45
Chapter 5 InsightPower SNMP IPv6 for UPS Web
NOTE
If the IP address is static and you wish to copy settings to other devices
on the same LAN, you must manually remove the following line IP=xxx.
xxx.xxx.xxx under the [System] section from the exported configura-
tion file. You can open the configuration file with text editors such as
Notepad and WordPad. To modify/ assign IP address for the SNMP IPv6,
please see
Chapter 4: System Configurations
.
z
z
SNMP Configuration
The SNMP Configuration includes settings saved in the Notification tab.
To download a configuration file, simply click Download. To upload a con-
figuration file, click Choose File, select the file you wish to upload, and click
Upload.
NOTE
If you need to modify the command lines, please do not delete the un-
modified ones. They should be left intact to assure the integrity of the
configuration file.
Upgrade
The Upgrade page shows the SNMP IPv6’s current firmware version. The Ad-
ministrator can use this page to update the SNMP IPv6’s firmware. Click Choose
File, select the file you wish to upload, and click Upload. The upgrade process
should take about one minute.